Engineering Industry Today

Irresistibly impressive

UK based power resistor manufacturer Cressall has pushed the boundaries to develop a new pre-insertion resistor (PIR) for use in high voltage direct current (HVDC) applications.
Published 09 December 2014

~ Leicester resistor specialist successfully designs and tests new PIR ~

UK based power resistor manufacturer Cressall has pushed the boundaries to develop a new pre-insertion resistor (PIR) for use in high voltage direct current (HVDC) applications. 

Historically, HVDC systems have been based on Line Commutated Converter (LCC) technology and Cressall has supplied many conventional high voltage resistors for use with this equipment in the past. 

Newer VSC (Voltage Source Converter) technology now offers a more compact solution and is used where space is restricted, such as on offshore wind farms. However with VSCs, resistors are needed to limit the very high currents developed upon start up due to the system capacitance, or ability to store an electrical charge. 

Cressall set out to design a resistor that could safely withstand the mechanical and thermal stresses of the 48MJ of energy that is applied for just one quarter of a second at switch on. Furthermore, because space is limited, the complete structure needed to occupy as small a footprint as possible – resulting in an assembly more than ten metres high.

Very high voltages can ionise air. Known as corona discharge, this ionisation can cause radio interference, reduce system efficiency and potentially damage equipment. Even when not absorbing energy, the resistor is still connected to the high voltage circuit and so corona discharge needs to be accounted for. 

Working with industry specialists, Cressall designed and fitted corona shields - smooth aluminium bars on the top and bottom of the structure that reduce the electrical stresses and evenly distributed the electrical field to minimise the potential for ionisation.

To prove that corona discharge would not be generated, the electrical stresses on the resistor were measured by conducting a radio interference voltage (RIV) test at 275kV.
 
“Because the voltages and energies are so high, we've had to systematically design and test the PIRs" explained Martin Nicholls, sales director at Cressall. "As well as the RIV tests, we have conducted high current density testing to confirm the design will safely absorb the high energies applied in such a short time. By impulse testing at 475kV, we've made sure that the insulation and the air gaps will not break down with the application of high voltages. 

"In addition, using Ansys design software, we've ensured that the structures can withstand wind speeds of up to 55mph. All in all, we are extremely pleased with how the PIRs responded to all testing."  